By clicking on the button “I accept” or by further usage of this website you express consent with usage of cookies as well as you grant us the permission to collect and process personal data about your activity on this website. More information about personal data processing can be found on this link. Read More

2026.11.18

Ampace Presents PU100 Fire Test Results at RE+ 2026, Advancing Safety for AI Data Centers

At RE+ 2026, we presented the results of our PU100 large-scale fire test (LSFT) under UL 9540A, 6th Edition, and received a test certificate from UL Solutions. The results demonstrated effective control of fire propagation, substantial margins below the assessed temperature limits, and no observed re-ignition for 24 hours after self-extinguishment—providing measurable evidence to support battery safety assessments for AI data centers.

“Safety is a core principle of our product design. For data center operators, the critical question is how effectively a battery system can limit the consequences of a failure,” said Dr. Drew Feng, our Chief Safety & Reliability Officer. “Through large-scale fire testing, we turn that question into measurable evidence—where propagation stops, how much heat reaches surrounding structures, and whether re-ignition occurs. These findings help customers make informed decisions about system selection, installation design and recovery planning.”

Ampace Presents PU100 Fire Test Results at RE+ 2026, Advancing Safety for AI Data Centers.PNG

Measurable results, practical value

The PU100 results provide evidence to help customers evaluate fault containment, thermal exposure, installation layouts and post-fire risks:

  • Containing the impact of a failure. Thermal runaway did not propagate to adjacent modules, and no fire spread to adjacent or target cabinets was observed. These findings support fault-isolation assessments and recovery planning.

  • Limiting heat exposure to surrounding structures. Wall temperature rise remained below 80°C against a 97°C limit, while ceiling steel-beam temperature stayed below 250°C against a 538°C limit. These margins help project teams assess potential thermal impacts on the facility.

  • Supporting compact installation planning. Testing involved 10 fully charged cabinets in a compact arrangement, including zero side-by-side clearance. The results provide an engineering reference for evaluating space-efficient deployment.

  • Demonstrating post-fire stability. With sprinklers armed but not activated, the fire self-extinguished after 43 minutes, followed by 24 hours without observed re-ignition. No flaming debris escaped the cabinet, providing evidence for assessing post-fire risks and potential impacts on nearby equipment.

These findings apply to the tested configuration and conditions and support project-specific engineering assessments.

The pursuit of ultimate safety

Ultimate safety is central to our product philosophy, extending beyond UPS batteries across our wider portfolio. Since our establishment in 2021, we have delivered battery packs and cells at scale across diverse applications while maintaining zero recorded safety incidents.

The PU100 results reflect our commitment to making safety measurable through product design, system engineering and rigorous testing. We will continue to translate validated findings into practical guidance, helping customers make informed decisions about the battery systems supporting their critical power infrastructure.